TECK90 (XLPE) 1000 Volts -40°C Copper

Four Conductor

ASTM Class B stranded soft bare copper. In sizes 8 AWG to 1000 kcmil, the conductors are compact stranded to reduce cable diameter and weight. Insulation is cross-linked polyethylene XLPE, the most widely used polymeric material for insulating both low and high voltage cables. The insulated conductors in the unshielded TECK cables rated 5 KV or less meet the requirement of CSA for RW90 XLPE. 

Packaging: Long length Reels, cut to length.

Construction & Technical Data

PCS
Catalogue
Number
Conductor Bonding Conductor Insulation
(inches)
Inner Jacket
(inches)

Approximate Diameters

Ampacity Total
Weight
(lbs/km)
No. AWG
Size
Inner Jacket  Armour Outer Covering
TKB14-04 4 14 14 .045 .045 .493 .733 .827 15 925
TKB12-04 4 12 14 .045 .060 .569 .809 .903 20 1,168
TKB10-04 4 10 12 .045 .060 .632 .878 .965 30 1,430
TKB08-04 4 8 10 .045 .060 .694 .921 1.028 45 1,913
TKB06-04 4 6 8 .060 .080 .895 1.170 1.351 65 2,749
TKB04-04 4 4 8 .060 .080 .995 1.270 1.441 85 3,681
TKB03-04 4 3 6 .060 .080 1.085 1.360 1.501 105 4,458
TKB02-04 4 2 6 .060 .080 1.145 1.420 1.663 120 5,183
TKB01-04 4 1 6 .080 .080 1.303 1.578 1.774 140 6,322
TKB001-04 4 1/0 6 .080 .080 1.394 1.669 1.865 155 7,530
TKB002-04 4 2/0 6 .080 .080 1.488 1.757 1.960 185 8,895
TKB003-04 4 3/0 4 .080 .080 1.607 1.852 2.141 210 11,139
TKB004-04 4 4/0 4 .080 .110 1.793 2.033 2.417 235 13,770
TKB250-04 4 250 4 .090 .110 1.952 2.033 2.542 265 15,843
TKB300-04 4 300 4 .090 .110 2.077 2.427 2.654 295 18,472
TKB350-04 4 350 3 .090 .110 2.189 2.539 2.833 325 20,995
TKB400-04 4 400 3 .090 .110 2.294 2.644 3.020 345 23,400
TKB500-04 4 500 3 .090 .110 2.481 2.831 2.757 395 28,068

**Where fourth conductor is neutral of a three phase, four-wire system; otherwise 80% of these values – CEC Rule 4-002(3).