TECK90 (XLPE) 600 Volts -40°C Copper

10AWG Multi-Conductor

ASTM Class B stranded soft bare copper. In sizes 8 AWG to 1000 kcmil, the conductors are compact stranded to reduce cable diameter and weight. Insulation is cross-linked polyethylene XLPE, the most widely used polymeric material for insulating both low and high voltage cables. The insulated conductors in the unshielded TECK cables rated 5 KV or less meet the requirement of CSA for RW90 XLPE.

Packaging: Long length Reels, cut to length.

Construction & Technical Data

PCS
Catalogue
Number
Conductor Bonding Conductor Insulation
(inches)
Inner Jacket
(inches)

Approximate Diameters

Ampacity Total
Weight
(lbs/km)
No. AWG
Size
Inner Jacket  Armour Outer Covering
TKA10-02 2 10 12 .030 .045 .452 .684 .769 30 892
TKA10-03 3 10 12 .030 .045 .481 .712 .798 30 1,112
TKA10-04 4 10 12 .030 .045 .560 .783 .867 30 1,256
TKA10-05 5 10 12 .030 .060 .604 .833 .918 30 1,381
TKA10-06 6 10 12 .030 .060 .671 .900 .985 30 1,696
TKA10-07 7 10 12 .030 .060 .699 .928 1.018 30 1,768
TKA10-08 8 10 12 .030 .060 .726 .954 1.047 30 2,024
TKA10-09 9 10 12 .030 .060 .766 1.006 1.094 30 2,076
TKA10-10 10 10 12 .030 .060 .840 1.100 1.188 30 2,546
TKA10-11 11 10 12 .030 .060 .879 1.135 1.222 30 2,608
TKA10-12 12 10 12 .030 .080 .917 1.178 1.266 30 2,903
TKA10-15 15 10 12 .030 .080 .987 1.247 1.335 30 3,465
TKA10-19 19 10 12 .030 .080 1.066 1.321 1.414 30 3,967
TKA10-20 20 10 12 .030 .080 1.098 1.357 1.445 30 4,235
TKA10-25 25 10 12 .030 .080 1.229 1.504 1.596 30 5,013
TKA10-30 30 10 12 .030 .080 1.317 1.573 1.680 30 5,807
TKA10-37 37 10 12 .030 .080 1.494 1.769 1.864 30 6,880
TKA10-40 40 10 12 .030 .080 1.567 1.917 1.967 30 7,539
TKA10-50 50 10 12 .030 .080 1.701 2.051 2.105 30 9,000
TKA10-60 60 10 12 .030 .110 1.910 2.260 2.314 30 10,837
TKA10-80 80 10 12 .030 .110 2.133 2.483 2.570 30 13,862
TKA10-90 90 10 12 .030 .110 2.246 2.596 2.683 30 15,276