USEI90/USC90 Triplex Underground Distribution Cable

Reduced

Compact stranded aluminum conductors, Black cross-linked polyethylene insulation, colour-coded PVC jacket. Two phase conductors plus one reduced neutral conductor. Rated 600 volts.

CSA C22.2 No.52

CEA WCWG-04 (02/93)

Applications:

PCS
Catalogue
Number
Phase Conductor Size
(AWG/MCM)
Neutral Conductor Size
(AWG/MCM)

Insulation Thickness

Jacket Thickness

Approximate Diameter

Total
Weight
(lbs/km)

Phase 

(inches)

Neutral 

(inches)

Phase 

(inches)

Neutral 

(inches)

Phase 

(inches)

Neutral 

(inches)

Overall 

(inches)

USEIR04-03

4

6

.045 .045 .030 .030 .378 .332 .784 726
USEIR02-03

2

4

.045 .045 .030 .030 .436 .378 .900 1,012
USEIR01-03

1

3

.060 .045 .045 .030 .520 .404 1.052 1,408
USEIR001-03

1/0

2

.060 .060 .045 .030 .560 .436 1.132 1,672
USEIR002-03

2/0

1

.060 .060 .045 .045 .600 .520 1.240 1,980
USEIR003-03

3/0

1/0

.060 .060 .045 .045 .648 .560 1.340 2,420
USEIR004-03

4/0

2/0

.060 .060 .045 .045 .704 .600 1.452 2,904
USEIR250-03

250

3/0

.070 .060 .070 .045 .808 .648 1.644 3,652
USEIR350-03

350

250

.070 .070 .070 .070 .912 .808 1.896 4,840
USEIR500-03

500

350

.070 .070 .070 .070 1.032 .912 2.144 6,490

 

Applications:

Underground Service Entrance Cable.