RWG90 FT4 Rated Grounding Cable 600 Volts 90°C Copper |
![]() |
![]() |
|
Single
bare solid or Class B stranded copper conductors, flame
retardant non-chlorinated cross-linked polyethylene XLP insulation. UL
Type XHHW (VW-1) and (Listed for CT Cable Tray use 1/0 and Larger),
C-UL Type RW90 FT4 (Type TC Tray Cable use 1/0 and Larger) |
| PCS Catalogue Number | Conductor | Insulation (inches) |
Ampacity (30°C
Ambient) Free Air |
Ampacity (30°C
Ambient) Conduit# | Nominal O.D. (inches) | Total Weight (lbs/km) | ||
|---|---|---|---|---|---|---|---|---|
| No. | AWG Size | Stranding | ||||||
| RWG14-1-XX | 1 | 14 | Solid | .045 | 20 | 15 | .155 | 53 |
| RWG12-1-XX | 1 | 12 | Solid | .045 | 25 | 20 | .175 | 79 |
| RWG10-1-XX | 1 | 10 | Solid | .045 | 40 | 30 | .195 | 118 |
| RWG14-7-XX | 1 | 14 | 7 Strand | .045 | 20 | 15 | .165 | 56 |
| RWG12-7-XX | 1 | 12 | 7 Strand | .045 | 25 | 20 | .185 | 82 |
| RWG10-7-XX | 1 | 10 | 7 Strand | .045 | 40 | 30 | .210 | 124 |
| RWG08-7-XX | 1 | 8 | 7 Strand | .060 | 70 | 45 | .270 | 203 |
| RWG06-7-XX | 1 | 6 | 7 Strand | .060 | 100 | 65 | .310 | 312 |
| RWG04-7-XX | 1 | 4 | 7 Strand | .060 | 135 | 85 | .355 | 479 |
| RWG03-7-XX | 1 | 3 | 7 Strand | .060 | 155 | 105 | .385 | 594 |
| RWG02-7-XX | 1 | 2 | 7 Strand | .060 | 180 | 120 | .415 | 741 |
| RWG01-19-XX | 1 | 1 | 19 Strand | .080 | 210 | 140 | .500 | 935 |
| RWG001-19-XX | 1 | 1/0 | 19 Strand | .080 | 245 | 155 | .540 | 1,165 |
| RWG002-19-XX | 1 | 2/0 | 19 Strand | .080 | 285 | 185* | .585 | 1,453 |
| RWG003-19-XX | 1 | 3/0 | 19 Strand | .080 | 330 | 210 | .635 | 1,814 |
| RWG004-19-XX | 1 | 4/0 | 19 Strand | .080 | 385 | 235 | .690 | 2,267 |
| RWG250-37-XX | 1 | 250 | 37 Strand | .080 | 425 | 265 | .740 | 2,690 |
| RWG350-37-XX | 1 | 350 | 37 Strand | .080 | 530 | 325 | .840 | 3,727 |
| RWG500-37-XX | 1 | 500 | 37 Strand | .080 | 660 | 395 | .970 | 5,262 |
| RWG600-61-XX | 1 | 600 | 61 Strand | .080 | 740 | 455 | 1.050 | 6,355 |
| RWG750-61-XX | 1 | 750 | 61 Strand | .080 | 845 | 500 | 1.155 | 7,897 |
| RWG1000-61-XX | 1 | 1000 | 61 Strand | .080 | 1000 | 585 | 1.305 | 10,446 |
| *For 3-wire 120/240
and 120/208V residential services or sub-services, the allowable
ampacity for sizes #6, #2 and #4/0 AWG aluminum shall be 60, 100 and
200 amperes respectively. #2/0 AWG copper shall be 200 amperes. In
these cases, the 5% adjustment per C.E. Code Rule 8-106(1) cannot be
applied.
For open wiring and raceways in dry or wet locations. For exposed wiring where exposed to weather with sunlight resistant insulation. |