| ACWU90 (–40°C) XLPE 600 Volts 90°C Aluminum | ![]() |
![]()
|
One to four aluminum conductors with low temperature cross-linked polyethylene insulation (RW90 XLPE) and bare aluminum bonding wire in multi-conductor cables. Single conductor cables have copper concentric bonding wire. Conductor assembly is wrapped and enclosed in an interlocked aluminum armour with an overall low acid gas and low flame spread PVC jacket (LAG/LFS) with FT4 and AG14 rating. H.L. rated for Class I Div 1 & 2 Groups A, B, C & D, Class II Div 1 & 2 Groups E, F & G and Class III Hazardous Locations. CSA Spec C22.2 No. 51-95. |
|
3 Conductor Insulation Colour Code:
Black, Red, White Ampacity in accordance with Table #4 of
the Canadian Electrical Code Part #1 (1994). **Assuming the 4th conductor in a 4/c cable is the neutral of a balanced 3 phase 4 wire system. For 3-wire 120/240 and 120/208V residential services or sub-services, the allowable Ampacity for sizes #6, #2 and #4/0 AWG aluminum shall be 60, 100 and 200 amperes respectively. In these cases the 5% adjustment per C.E. Code Rule 8-106(1) cannot be applied.
For
exposed and concealed wiring in dry or wet locations and where exposed
to the weather. |